TeSys GV3-Circuit breaker-thermal-magnetic-30…40A-EverLink BTR/direct connectors. range: TeSys - product name: TeSys GV3 - device short name: GV3P - product or component type: circuit breaker - device application: motor - network type: AC - utilisation category: AC-3 conforming to IEC 60947-4-1, category A conforming to IEC 60947-2 - breaking capacity: 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 - [Ics] rated service short-circuit breaking capacity: 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2, 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2, 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 - magnetic tripping current: 560 A. Benefits: A stronger, safer, and long-term connection. Designed with the new and ingenious, EverLink* patented, power terminal system, TeSys GV3 circuit-breaker provides a more reliable connection quality: the tightening pressure applied to the cables remain stable, strong and long-lasting even under tough conditions. Common additive parts to GV2 and GV3 ranges provide simplicity and significant installation time saving.... Applications: - Industry, infrastructures, buildings: Used for motor control and protection, complying with IEC 947-2 and IEC 947-4-1 standards... *Schneider patent....

Product details

Technical specifications

Overload release current setting30 ... 40 A
Adjustment range undelayed short-circuit release560 ... 560 A
With thermal protectiontrue
Phase failure sensitivetrue
Switch off techniqueThermomagnetic
Rated operating voltage0 ... 690 V
Rated permanent current Iu40 A
Rated operation power at AC-3, 230 V11 kW
Rated operation power at AC-3, 400 V18.5 kW
Type of electrical connection of main circuitScrew connection
Type of control elementTurn button
Device constructionComplete device in housing
With integrated auxiliary switchfalse
With integrated under voltage releasefalse
Number of poles3

Product codes

SAPAEW219
PLC3760216
STK3760216
GTIN/EAN3389119412254
Manufacturer part numberGV3P401
Vendor material number3760216

Basic information

Package measurements (L x W x H)65 x 145 x 145 mm
Package volume1.508 l
Package weight0.94 kg
Base uniteach
Package units1 / 120
Package contents
UNSPSC39121521
BrandSCHNEIDER ELECTRIC
VendorSCHNEIDER ELECTRIC FINLAND OY